Skip to the content
TOTAL PRODUCT RECALL
CPSC #01507Other
Recalled Combination Gas Furnace and Electric Air Conditioning Unit

Trane Company · Recalled

CPSC, Trane Company Announce Recall of Voyager Heating and Air Conditioning Systems

Carbon monoxide

One of the three internal flue gas tubes extending from the heat exchanger can separate from the heat exchanger. This could allow flue gases, including carbon monoxide, to enter the building airstream. This could result in serious injury or death to building occupants.

Units
967
Reports
—
Injuries
—
Deaths
0
Price
—
Remedy
See notice

Reports, injuries, deaths and price are read out of the notice’s wording by rules, so they can miss unusual phrasing. The official notice is the record.

Affected

The Voyager series of light commercial rooftop air conditioners with electric cooling and gas-fired heat exchangers, which are installed in schools and commercial applications, have 120,000 to 135,00 BTU heating capacity and three- to five-ton cooling capacity in horizontal and downflow configurations. The Voyager series has been manufactured by Trane since 1988 and is distributed under the Trane® and American Standard® brand names. The recalled units were manufactured between June 1, 2000 and August 16, 2000 and have serial numbers beginning with R21 through and including R33. The recalled products include the following model designations: YCD036C1H_ _ _ YCD060CWH_ _ _ YCD048C1H_ _ _ YCH060C1H_ _ _ YCH048C1H_ _ _ YCH060C3H_ _ _ YCD060C1H_ _ _ YCH060C4H_ _ _ YCD060C1H_ _ _ YCD060C3H_ _ _ YCD060C4H_ _ _ A name plate bearing each unit's model and serial number is located on the outside sheet metal at the end of the unit where the propeller fan is visible on top, directly to the left of the exposed outdoor coils.

The file

Sold at
Not stated
Product type
Air Conditioners
Made in
Not stated
Recalled by
The Trane Company, of Tyler, Texas, a division of American Standard Companies Inc.

Incident log

None reported.

What the notice says to do

Call the local independent Trane or American Standard dealer for a free inspection and replacement, if needed. Trane will completely replace the heat exchanger end plate and internal flue gas tube assemblies in all recalled units at no cost to the consumer.

For assistance in locating a local independent dealer, contact Trane at (800) 940-1344 between 7:30 a.m. and 4:30 p.m. CT Monday through Friday, or visit the firm's web site at www.trane.com

Open official CPSC notice ↗ (opens in a new tab)

Recall notice published by the U.S. Consumer Product Safety Commission. This site is independent: always confirm on the official notice before acting.

Notice first dated JAN 24 2001; last revised APR 14 2026.

All 2001 recalls · Back to the timeline