NO MEMORY IMAGE ON FILE
Invensys Building Systems · Recalled
CPSC, Invensys Building Systems Announce Recall of Siebe Actuators in Building Fire/Smoke Dampers
A spring mechanism integrated with the damper is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.
- Units
- Up to 560,000
- Reports
- —
- Injuries
- —
- Deaths
- —
- Price
- —
- Remedy
- See notice
Reports, injuries, deaths and price are read out of the notice’s wording by rules, so they can miss unusual phrasing. The official notice is the record.
Affected
These MA-200 and MA-200-1 series actuators were used in fire and smoke dampers that were manufactured by various companies from December 1993 through October 1999, which were installed by private contractors in commercial and residential buildings. The actuators have manufacture date codes of 9348 through 9947. See the associated recall alert for more details on the dampers and companies involved.
The file
- Sold at
- Not stated
- Product type
- Dampers
- Made in
- United States
- Recalled by
- Invensys Building Systems, of Love Park, Ill.
Incident log
Building owners, damper manufacturers, and fire and safety investigators have reported dampers not closing during testing.
What the notice says to do
To be eligible for a free actuator replacement, the building owner must test the actuator and report the results to Invensys. Only actuators that fail testing will be replaced.
Building owners and managers whose buildings have dampers containing Invensys/Siebe actuators should immediately contact Invensys' Program Coordination Office at (877) 481-2372 between 7 a.m. and 7 p.m. CT Monday through Friday. A web site where building owners can obtain a complete copy of the program information has been established at www.regcen.com/MA200
Recall notice published by the U.S. Consumer Product Safety Commission. This site is independent: always confirm on the official notice before acting.
Notice first dated OCT 02 2002; last revised APR 25 2025.