Greenheck Fan Corp. · Recalled
CPSC, Greenheck Fan Corp. Announce Recall of Ventilation Units
LUX 3/8-inch spinlock bolts supplied with these units may not have been properly heat treated, which can result in the bolts breaking. Bolt failure during lifting for rooftop installation or after installation could cause the unit or components to fall and injure bystanders.
- Units
- About 4,200 ventilation units
- Reports
- —
- Injuries
- —
- Deaths
- 0
- Price
- —
- Remedy
- See notice
Reports, injuries, deaths and price are read out of the notice’s wording by rules, so they can miss unusual phrasing. The official notice is the record.
Affected
Affected units are Sidewall, Rooftop and Centrifugal Inline ventilation units built between August 11, 2004 and April 29, 2005, containing 16-thread-per-inch 3/8-inch by ¾-inch spinlock bolts with LUX head markings. Affected model numbers are RBU, RBUMO, RDU, RB/R, SB/S, and BSU 360-420 with serial numbers 04HXXXXX through 05DXXXXX. The model and serial numbers are found on metal identification plate on the units.
The file
- Sold at
- Independent sales representatives and original equipment manufacturers, from August 2004 through July 2005.
- Product type
- Ventilators
- Made in
- Taiwan
- Recalled by
- Greenheck Fan Corp., of Schofield, Wis.
Incident log
Greenheck is aware that 309 LUX bolts that have failed in the field. There are no reports of ventilation units falling or any injuries.
What the notice says to do
LUX spinlock bolts in affected units will be replaced at no cost to the end user.
Affected sales representatives and original equipment manufacturers are being contacted directly. For additional information, contact Greenheck at (800) 931-6579 between 8 a.m. and 5 p.m. CT Monday through Friday, or email Kathy.Lenard@greenheck.com
Recall notice published by the U.S. Consumer Product Safety Commission. This site is independent: always confirm on the official notice before acting.
Notice first dated SEP 30 2005; last revised JAN 02 2025.