Skip to the content
TOTAL PRODUCT RECALL
CPSC #07062Other
Recalled Safety Switch

Square D · Recalled

Square D Recalls Safety Switches Due to Shock or Electrocution Hazard

Electric shock

The safety switch can continue to supply electricity even after being placed in the "OFF" position. This poses the risk of an electric shock or electrocution hazard to consumers.

Units
About 27,600
Reports
—
Injuries
—
Deaths
0
Price
$120–$300
Remedy
See notice

Reports, injuries, deaths and price are read out of the notice’s wording by rules, so they can miss unusual phrasing. The official notice is the record.

Affected

The recall includes General Duty 30- and 60-ampere, 240-volt, 1-phase and 3-phase NEMA 3R safety switches. The switches are typically used to control the flow of electricity to outdoor motorized units that are hardwired to a household or business electrical system such as outdoor air conditioning and heating (HVAC) equipment. The switches contain "ON" and "OFF" positions. The "OFF" position is designed to cut the flow of electricity to an outdoor motorized unit to protect the person who is servicing the unit. The recalled switches have the following date codes and catalog number printed on bottom of the wiring label inside the front cover or on bottom of the package label. Date Codes 06371 through 06446 Catalog Numbers D211NRB D211NRBBP D211NRBCP D221NRB D221NRBCP D321NRB D321NRBCP DU221RB DU222RB DU321RB DU322RB

The file

Sold at
Electrical distributors and retailers from September 2006 through November 2006 for between $120 and $300.
Product type
Switches
Made in
Mexico
Recalled by
Square D Co., of Palatine, Ill.

Incident log

No incidents or injuries have been reported.

What the notice says to do

Consumers should return the uninstalled safety switches to the retailer or distributor where purchased for a free replacement unit. Installed safety switches will be replaced free of charge by contacting the firm.

Contact Square D toll-free at (877) 202-9046 between 7:30 a.m. and 5 p.m. ET Monday through Friday, or visit the firm's Web site at www.us.squared.com

Open official CPSC notice ↗ (opens in a new tab)

Recall notice published by the U.S. Consumer Product Safety Commission. This site is independent: always confirm on the official notice before acting.

Notice first dated DEC 15 2006; last revised MAY 23 2014.

All 2006 recalls · Back to the timeline