Recalled Air Conditioner

Trane · Recalled

Trane Recalls Air Conditioners after Incidents of Units Smoking

Fire & burns

The heating element on these commercially installed units can become displaced and, if it contacts metal, could short circuit. If the electric heater on one of those units short-circuits, wiring problems on 265-volt models could allow the unit to remain energized while the unit's fan is turned off, causing it to overheat and smoke.

Units
About 10,580
Reports
—
Injuries
—
Deaths
—
Price
—
Remedy
See notice

Reports, injuries, deaths and price are read out of the notice’s wording by rules, so they can miss unusual phrasing. The official notice is the record.

Affected

The recall includes 208-, 230- and 265-volt models of the Trane PTEE and PTHE Series Packaged Terminal Air Conditioners (PTACs). They were manufactured from about March 2006 through July 2006. The date code is F06C through F06G, and is written on the unit's Manufacturer's Data Plate located behind the molded plastic cover above the power connection. The units have the following model numbers, also written on the Manufacturer's Data Plate: PTEE0701UAA PTEE1501UAA PTHE0902UAA PTEE0702UAA PTEE1502UAA PTHE1201UAA PTEE0901UAA PTHE0701UAA PTHE1202UAA PTEE0902UAA PTHE0702UAA PTHE1501UAA PTEE1201UAA PTHE0901UAA PTHE1502UAA PTEE1202UAA

The file

Sold at
Trane distributors sold the recalled units to commercial customers for use in locations such as hotels and office buildings from May 2006 to July 2006.
Product type
Air Conditioners
Made in
China
Recalled by
Qingdao Haier Air Conditioner, of Qingdao, China, The Trane Co., of Piscataway, N.J.

Incident log

Individuals installing units observed smoking and smelled a burning odor in three units during installation testing procedures. No injuries have been reported.

What the notice says to do

The power connectors are being rewired or replaced, and the heaters will be visually inspected and replaced as necessary in the 265-volt models. Although there have been no incidents with the 208-volt and 230-volt models, Trane is still inspecting these units as a precaution. Trane has contacted the affected customers directly.

For more information, contact Trane at (800)235-2152 or at (931) 648-5047, between 9 a.m. and 4:30 p.m. ET Monday through Friday, or write an email to buddy.sholar@trane.com

Open official CPSC notice ↗ (opens in a new tab)

Recall notice published by the U.S. Consumer Product Safety Commission. This site is independent: always confirm on the official notice before acting.

Notice first dated NOV 30 2006; last revised MAY 23 2014.