Recalled Bosch fire control panel

Bosch Security Systems · Recalled

Fire Control Panels Recalled by Bosch Security Systems Corp. Due to Alarm Failure Posing a Fire Hazard

Fire & burns

On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.

Units
About 330
Reports
—
Injuries
—
Deaths
0
Price
$1,200
Remedy
See notice

Reports, injuries, deaths and price are read out of the notice’s wording by rules, so they can miss unusual phrasing. The official notice is the record.

Affected

The Bosch-branded fire alarm panel is locking red wall box with dimensions 22.7" high by 14.5" wide by 4.3" deep. The status, date and time can be seen through a glass screen on the panel door. The word "BOSCH" is printed on the right corner of the panel and the model number "FPA-1000-UL" is printed on the bottom left below the glass screen. The alarm panels featured software versions 1.10, 1.11 and 1.12, which can be determined by installers. They were designed to be used in small to medium-sized facilities in both public and residential buildings.

The file

Sold at
Authorized distributors and installers nationwide from May 2009 through October 2011 for about $1,200.
Product type
Fire or Smoke Alarms
Made in
China
Recalled by
Bosch Security Systems, Inc., of Fairport, N.Y.

Incident log

None reported.

What the notice says to do

All distributors and installers are being sent two technical bulletins. One provides instructions for how to implement a software change that will correct the verification feature. The second contains instructions for how to handle warnings from affected systems with 50 or more stations. Those who have not received the bulletins should contact Bosch.

For more information, contact Bosch Security Systems at (800) 289-0096 between 8:00 a.m. and 8:00 p.m. ET or visit service/customer care on the firm's website at http://www.boschsecurity.us/en-us/ for instructions on how to download software to update the control panels or otherwise address the problems.