Skip to the content
TOTAL PRODUCT RECALL
CPSC #14713Home & furniture
System Sensor smoke detectors

System Sensor · Recalled

System Sensor Recalls Reflected Beam Smoke Detectors Due To Failure to Alert Consumers in a Fire (Recall Alert)

Fire & burns

When used with certain power supplies, the reflected beam smoke detectors can fail to send a signal to the fire alarm control panel that sounds the alarm and fail to alert occupants of a fire.

Units
About 610
Reports
—
Injuries
—
Deaths
0
Price
$800
Remedy
Replace

Reports, injuries, deaths and price are read out of the notice’s wording by rules, so they can miss unusual phrasing. The official notice is the record.

Affected

This recall involves System Sensor's reflected beam smoke detectors with model number BEAM1224S and date codes 2111 through 3053. The YMMW format date codes stand for (2111) 2012-November-1st week of Nov. through (3053) 2013-May-3rd week of May. The detectors are ivory and black and measure 10 inches high by 7½ inches wide. The model number and date code are printed on a label on the back of the detector's cover and on the product's packaging. The reflected beam smoke detectors were used primarily in commercial buildings as part of the fire alarm system. Detectors used with acceptable power supplies, as listed on the company website, do not need to be replaced.

The file

Sold at
Alarm system, security equipment and electrical equipment contractors and dealers for use in commercial building fire alarm systems from November 2012 through May 2013 for about $800.
Product type
Fire or Smoke Alarms
Made in
United States
Recalled by
System Sensor, of St. Charles, Ill.

Incident log

None reported

What the notice says to do

Owners with the affected smoke detectors powered by a power supply that is not on the company's acceptable list available online, should contact System Sensor to receive free replacement smoke detectors. System Sensor and its distributors are contacting purchasers directly.

System Sensor at (800) 736-7672 from 7:30 a.m. through 5 p.m. CT Monday through Friday, or online at www.systemsensor.com and click on Resources, then Product Info Library/Technical Field Bulletins, then Safety Bulletins for more information and a list of acceptable power supplies.

Open official CPSC notice ↗ (opens in a new tab)

Recall notice published by the U.S. Consumer Product Safety Commission. This site is independent: always confirm on the official notice before acting.

Notice first dated JAN 28 2014; last revised MAY 11 2015.

Label on System Sensor smoke detectorsLabel on carton for System Sensor smoke detectors